getlicenseready
Back to Blog

NEC Articles 404 & 406 — Switches and Receptacles: The Complete Exam Guide

April 25, 20268 min readBy GetLicenseReady Team

Articles 404 and 406 govern two of the most common devices electricians install: switches and receptacles. While neither article is as voluminous as Article 250 or 430, they contain highly specific rules that appear on virtually every residential and commercial exam — particularly around ratings, tamper resistance, weatherproofing, and grounding.


NEC Article 404 — Switches

Article 404 covers the general requirements for all types of switches: snap switches, motor-circuit switches, and other disconnecting switches used in electrical installations.

404.2 — Switch Connections

The fundamental rule: every switch must open the ungrounded (hot) conductor, never the grounded (neutral).

Exam tip: A switch wired in series with the neutral is a code violation — the load remains energized with the switch "off." This is both a safety hazard and a violation of 404.2(A). Switches go in the hot leg, always.

Three-way switches: Where two three-way switches control the same load, the travelers connect the two switch boxes. The common terminal of each three-way switch connects to either the hot supply or the switched hot going to the load.

Grounded conductor (neutral) through a switch box: When a cable is run to a switch location and the neutral is needed to complete a circuit, the neutral passes through without interruption. The switch only opens the ungrounded conductor.


404.4 — Damp or Wet Locations

Switches installed in damp or wet locations must be enclosed in weatherproof enclosures.


404.6 — Position of Knife Switches

Knife switches must be mounted so the blades are de-energized when the switch is in the open position.

Single-throw knife switches must be mounted vertically such that gravity will not close the switch — blades up when closed, blades down when open.


404.9 — Position and Connection of Snap Switches

404.9(A): Snap switches must clearly indicate whether they are in the open (off) or closed (on) position. For vertically operated switches, up = ON, down = OFF.

404.9(B) — Grounding: Snap switches, including dimmer switches, must be connected to an equipment grounding conductor to allow grounding of a metal faceplate.

Exception: In existing installations where no grounding means exists in the switch box, the switch may be installed without connecting to an EGC if a nonmetallic, nonconducting faceplate is used, or if the switch itself is GFCI protected.

Exam tip: The grounding exception only applies to existing installations where no ground wire is present. New construction must always have the switch yoke grounded.


404.10 — Mounting of Snap Switches

Snap switches must be mounted with the yoke seated against the wall surface or box. The switch must be flush with the faceplate or recessed — not protruding.


404.14 — Ratings Required

404.14(A) — AC General-Use Snap Switches

A general-use snap switch marked for AC only may be used to control:

  • Resistive and inductive loads up to the ampere and voltage rating of the switch
  • Motor loads not exceeding 80% of the switch's ampere rating

404.14(B) — AC-DC General-Use Snap Switches

An AC-DC rated switch may control resistive loads up to its full rating on AC or DC circuits. For inductive loads on DC, the switch must be derated.

404.14(C) — CO/ALR Switches

Switches used with aluminum conductors must be marked CO/ALR. Switches marked only for copper may not be used with aluminum wire.

Exam tip: CO/ALR marking is required for switches and receptacles used with aluminum wiring — a common exam question for service-upgrade or older home work.


404.15 — Markings

Snap switches must be marked with:

  • Current rating
  • Voltage rating
  • Whether AC-only or AC-DC

Key Article 404 Numbers

RuleRequirement
Switch must openUngrounded (hot) conductor only
Vertical snap switch positionUp = ON, Down = OFF
Switch with metal yoke/plateMust connect to EGC
Motor load on general-use switchMax 80% of switch ampere rating
Aluminum wiringCO/ALR marking required

NEC Article 406 — Receptacles, Cord Connectors, and Attachment Plugs

Article 406 covers the selection, installation, and replacement of receptacles — one of the highest-volume topics on residential exams.


406.3 — Receptacle Rating and Type

15A vs 20A receptacles on branch circuits — this is the most-tested provision in Article 406:

210.21(B) — Single receptacle: A single (individual) receptacle outlet installed on a branch circuit must have an ampere rating no less than that of the branch circuit.

Circuit RatingSingle Receptacle Required
15A circuit15A receptacle minimum
20A circuit20A receptacle minimum

210.21(B) — Multiple receptacle outlet: Where a circuit supplies multiple receptacles or outlets, the receptacle rating must conform to Table 210.21(B)(3):

Circuit RatingReceptacle Rating Permitted
15A15A
20A15A or 20A
30A30A
40A40A or 50A
50A50A

Exam tip: The critical rule: a 15A receptacle is permitted on a 20A multi-outlet circuit. A 20A single outlet requires a 20A T-slot receptacle. This distinction appears on almost every residential journeyman exam.


406.4 — General Installation Requirements

406.4(A) — Circuit Voltage: Receptacles must not be installed on circuits with a voltage exceeding the receptacle rating.

406.4(B) — Grounding Type: Receptacles installed on grounded systems (standard 120V/240V circuits) must be of the grounding type (three-prong).

406.4(D) — Replacements: When replacing a receptacle in a location that requires GFCI protection per 210.8, the replacement receptacle must be GFCI protected. This applies even in older homes where the original receptacle was two-prong and non-GFCI.

Replacement with a GFCI receptacle or a standard receptacle downstream of a GFCI breaker both satisfy this requirement. The replacement does not have to be a grounding-type if no grounding means is available — the GFCI protection is the safety element.

Exam tip: 406.4(D) is frequently tested in scenarios about replacing old two-prong outlets. In a kitchen or bathroom without a ground wire: replace with a GFCI receptacle (not required to be grounding-type, but must be GFCI protected) and mark it "No Equipment Ground."


406.9 — Receptacles in Wet and Damp Locations

406.9(A) — Damp Locations:

Receptacles in damp locations must have a weatherproof cover. The cover must maintain weatherproofing with no attachment plug inserted. A standard in-use weatherproof cover (listed for damp locations) is acceptable.

406.9(B) — Wet Locations:

Receptacles installed in wet locations must be protected by an in-use cover listed as extra-duty, which maintains weatherproofing even with a cord plugged in (sometimes called a "bubble cover").

LocationRequired Cover
Damp (covered, weather-exposed)Weatherproof cover (no cord)
Wet (direct rain/moisture exposure)Extra-duty in-use cover (with cord)

Exam tip: Damp vs wet — a covered porch is damp; an exposed outdoor wall is wet. The exam often describes a scenario and asks which cover is required. Extra-duty in-use = wet location. Standard weatherproof = damp location.


406.11 — Tamper-Resistant Receptacles in Dwelling Units

All 15A and 20A, 125V receptacles in dwelling units must be tamper-resistant. This includes:

  • Every room, hallway, and common area
  • Garages and accessory structures
  • Outdoors
  • Crawl spaces and unfinished basements
  • Kitchen and dining countertops

Exceptions: Receptacles located more than 5½ feet above the floor, receptacles that are part of a luminaire or appliance, locked receptacles accessible only to qualified persons, and non-grounding-type replacements where no grounding means is available.

Exam tip: In any new construction dwelling unit, ALL 15A/20A 125V receptacles must be tamper-resistant — not just those in children's rooms. This requirement applies building-wide.


406.12 — Receptacles in Specific Locations

Face-up receptacles in countertops — a receptacle installed in a countertop face-up (horizontal) must be listed and identified for that use. Standard outlet boxes installed face-up in a countertop are not permitted unless specifically listed for countertop installation.

CO/ALR receptacles — receptacles used with aluminum conductors must be marked CO/ALR. Standard receptacles marked only for copper cannot be used with aluminum wiring.


Key Article 406 Numbers

RuleRequirement
Single outlet on 20A circuitMust be 20A rated receptacle
15A receptacle on 20A multi-outlet circuitPermitted (Table 210.21(B)(3))
Replacement in GFCI-required locationMust be GFCI protected (406.4(D))
Wet location coverExtra-duty in-use cover
Damp location coverStandard weatherproof cover
Tamper-resistant in dwelling unitsAll 15/20A 125V outlets
Aluminum wiringCO/ALR marking required

Common Exam Mistakes on Articles 404 & 406

  1. Wiring a switch in the neutral leg — always in the ungrounded conductor; the load stays hot with the switch off if wired wrong
  2. Installing a 15A single-outlet receptacle on a 20A dedicated circuit — a single 20A circuit requires a 20A receptacle; 15A is only OK when there are multiple outlets
  3. Using a standard weatherproof cover in a wet location — wet requires extra-duty in-use cover; standard covers don't protect when a cord is plugged in
  4. Forgetting tamper-resistant applies to the whole dwelling — not just bedrooms; every 15/20A 125V outlet in the building
  5. Replacing a two-prong outlet without GFCI in a required location — 406.4(D) requires GFCI protection on all replacements in locations covered by 210.8

Ready to Practice Articles 404 & 406 Questions?

GetLicenseReady includes questions on switch ratings, receptacle rules, tamper-resistant requirements, and wet/damp location covers — the specific scenarios that appear on residential and commercial exams.

Ready to test your NEC knowledge?

1,600+ practice questions with step-by-step explanations.

Start Practicing Free →

Related reading: NEC Article 210 — Branch Circuits | NEC Article 110 — Requirements for Electrical Installations | GFCI and AFCI Requirements

Study for Your State's Exam

Select your state for license requirements, exam format, and state-specific prep tips.

Ready to Pass Your Electrician Exam?

Prepare for your electrician licensing exam with GetLicenseReady. 1,600+ practice questions with detailed NEC references.

Start Practicing Free