NEC Voltage Drop Calculator
Calculate voltage drop per NEC 210.19(A) and 215.2(A) recommendations. Free, no account required.
Circuit Details
6.60% voltage drop
Exceeds NEC recommended 3% maximum. Consider upsizing the conductor.
NEC Voltage Drop Recommendations
NEC 210.19(A) Informational Note No. 4: Branch circuits should not exceed 3% voltage drop. The total voltage drop for feeder and branch circuit combined should not exceed 5%.
NEC 215.2(A) Informational Note No. 2: Feeders should be sized so that the voltage drop is not more than 3% at the farthest outlet of power, heating, and lighting loads.
Note: These are recommendations (informational notes), not mandatory code requirements. However, they are frequently tested on electrician licensing exams and considered best practice.
Common Voltage Drop Scenarios
| Circuit | Wire | Max Distance (3%) |
|---|---|---|
| 20A, 120V | 12 AWG Cu | 45 ft |
| 20A, 240V | 12 AWG Cu | 90 ft |
| 30A, 240V | 10 AWG Cu | 96 ft |
| 40A, 240V | 8 AWG Cu | 115 ft |
| 50A, 240V | 6 AWG Cu | 146 ft |
Practice voltage drop calculations and 1,600+ more NEC questions
Timed exam simulations, step-by-step explanations, all 50 states.
Start Practicing Free →Get NEC Study Tips + Free Practice Questions
Join electricians prepping for their license exam. We send NEC tips and practice problems weekly.
No spam. Unsubscribe anytime.
This calculator uses DC resistance values from NEC Chapter 9 Table 8 at 75°C. AC circuits may have slightly different effective impedance due to reactance. Always verify with your local AHJ and the current NEC edition adopted in your jurisdiction.