GetLicenseReady

NEC Voltage Drop Calculator

Calculate voltage drop per NEC 210.19(A) and 215.2(A) recommendations. Free, no account required.

Circuit Details

6.60% voltage drop

Exceeds NEC recommended 3% maximum. Consider upsizing the conductor.

Conductor resistance1.9800 Ω/1,000 ft (copper, 75°C)
Formula: Vd = 2 × L × R × I / 10002 × 100 × 1.9800 × 20
Voltage drop7.92 V
Percent drop6.60%
Voltage at load112.1 V
0%3% recommended max5%

NEC Voltage Drop Recommendations

NEC 210.19(A) Informational Note No. 4: Branch circuits should not exceed 3% voltage drop. The total voltage drop for feeder and branch circuit combined should not exceed 5%.

NEC 215.2(A) Informational Note No. 2: Feeders should be sized so that the voltage drop is not more than 3% at the farthest outlet of power, heating, and lighting loads.

Note: These are recommendations (informational notes), not mandatory code requirements. However, they are frequently tested on electrician licensing exams and considered best practice.

Common Voltage Drop Scenarios

CircuitWireMax Distance (3%)
20A, 120V12 AWG Cu45 ft
20A, 240V12 AWG Cu90 ft
30A, 240V10 AWG Cu96 ft
40A, 240V8 AWG Cu115 ft
50A, 240V6 AWG Cu146 ft

Practice voltage drop calculations and 1,600+ more NEC questions

Timed exam simulations, step-by-step explanations, all 50 states.

Start Practicing Free →

Get NEC Study Tips + Free Practice Questions

Join electricians prepping for their license exam. We send NEC tips and practice problems weekly.

No spam. Unsubscribe anytime.

This calculator uses DC resistance values from NEC Chapter 9 Table 8 at 75°C. AC circuits may have slightly different effective impedance due to reactance. Always verify with your local AHJ and the current NEC edition adopted in your jurisdiction.