Skip to main content
getlicenseready

NEC Wire Ampacity Calculator

Copper conductor ampacity from NEC Table 310.16 with temperature correction and conductor count derating. Free. No account required.

Wire & Conditions

Auto-selects temperature column: 90°C / 194°F

No derating (1–3 conductors)

Ampacity Result

NEC Table 310.16, Copper, 90°C / 194°F column

Adjusted Ampacity

30.0A

Step-by-step calculation

Step 1Base ampacity, 12 AWG, 90°C / 194°F column (NEC Table 310.16)
30 A
Step 2Ambient temperature correction factor, 30°C (86°F) × NEC Table 310.15(B)(1)(1)
× 1.00
After temp correction (30 × 1.00)= 30.00 A
Step 3Conductor count derating, 3 conductors (NEC Table 310.15(C)(1))
× 100%
Final adjusted ampacity (30.00 × 1.00)= 30.0 A

NEC Table 310.16, Quick Reference (Copper, 60/75/90°C)

Size60°C75°C90°C
14 AWG15*2025
12 AWG20*2530
10 AWG303540
8 AWG405055
6 AWG556575
4 AWG708595
3 AWG85100115
2 AWG95115130
1 AWG110130145
1/0 AWG125150170
2/0 AWG145175195
3/0 AWG165200225
4/0 AWG195230260
250 kcmil215255290
300 kcmil240285320
350 kcmil260310350
400 kcmil280335380
500 kcmil320380430
600 kcmil350420475
700 kcmil385460520
750 kcmil400475535
800 kcmil410490555
900 kcmil435520585
1000 kcmil455545615

* Per NEC 240.4(D), overcurrent protection limited to 15A for 14 AWG, 20A for 12 AWG, 30A for 10 AWG.

Master wire ampacity and 1,600+ more NEC questions

Timed exam simulations, all 50 states, NEC code references on every answer.

Start Practicing Free →

Get NEC Study Tips + Free Practice Questions

NEC tips, practice questions, and exam strategies to help you pass. Unsubscribe anytime.

No spam. Unsubscribe anytime.

This calculator references NEC Table 310.16 values. Always verify with your local Authority Having Jurisdiction (AHJ) and the current NEC edition adopted in your jurisdiction. Values shown are for copper conductors only.

NEC Table 310.16NEC 310.15(B)NEC 310.15(C)(1)NEC 110.14(C)

How the wire ampacity calculation works

Ampacity is the current a conductor can carry continuously without exceeding its temperature rating. Table 310.16 gives the base value for insulated conductors rated up to 2,000 V, in raceway, cable, or direct buried, with not more than three current-carrying conductors, at an ambient of 30 degrees C.

Those three conditions in the table heading are the whole game. Break any of them and the base number has to be corrected. Above or below 30 C ambient you apply the correction factors in 310.15(B)(1). With more than three current-carrying conductors bundled or in the same raceway for more than 24 inches you apply the adjustment factors in 310.15(C)(1). When both apply you multiply them together.

Then 110.14(C) caps everything. Even if the conductor's 90 C column allows more, the terminations set the ceiling: 60 C for equipment rated 100 A or less unless it is listed otherwise, 75 C for larger equipment. The standard exam approach is to start from the 90 C column for correction and adjustment, since insulation temperature is what those factors address, then compare the corrected result against the 60 or 75 C termination limit and take the lower.

Step by step

  1. 1

    Pick the base ampacity

    Table 310.16, correct column for the insulation temperature rating (60, 75, or 90 C) and the right material.

  2. 2

    Apply ambient correction

    Table 310.15(B)(1) if the ambient is anything other than 30 C.

  3. 3

    Apply bundling adjustment

    Table 310.15(C)(1) if more than three current-carrying conductors run together more than 24 inches. Neutrals count only when they carry unbalanced current, 310.15(E).

  4. 4

    Multiply the factors

    Corrected ampacity = base x ambient factor x adjustment factor.

  5. 5

    Apply the termination limit

    110.14(C). Compare against the 60 C or 75 C column value for the same size and take the lower of the two.

  6. 6

    Size the overcurrent device

    240.4 and 240.4(B), with the small-conductor rules in 240.4(D) for 14, 12, and 10 AWG.

Worked example

Six current-carrying 8 AWG THHN copper conductors share a raceway in a 45 degree C ambient. Equipment is rated 75 C. What is the usable ampacity?

  1. Table 310.16, 90 C copper column, 8 AWG = 55 A.
  2. Table 310.15(B)(1), 41 to 45 C ambient at 90 C rating = 0.87.
  3. Table 310.15(C)(1), 4 to 6 conductors = 80 percent.
  4. 55 x 0.87 x 0.80 = 38.3 A.
  5. 110.14(C) check: 75 C column for 8 AWG copper = 50 A. The corrected 38.3 A is lower, so it governs.

Answer: 38.3 A. Per 240.4(B) the next standard overcurrent device above the ampacity is permitted here, which is 40 A, provided the conductors do not supply receptacle outlets and 40 A is not above the next standard rating.

How this is tested on the exam

This is the highest-frequency calculation on journeyman exams, and the most common way to get it wrong is to skip 110.14(C). Candidates correct off the 90 C column, land on a number bigger than the 75 C termination allows, and answer with the uncorrected figure. Start at 90 C for the factors, finish at the termination temperature.

Frequently asked questions

Which temperature column do I start in?

Start in the column matching the conductor's insulation rating, which for THHN and XHHW-2 is 90 C, and apply your ambient and bundling factors there. Then apply 110.14(C) and drop to the 60 or 75 C column value if that is lower. You do not get to use the 90 C ampacity as the final answer just because the wire is rated 90 C.

When do more than three conductors trigger derating?

310.15(C)(1) applies when more than three current-carrying conductors are bundled together or in a raceway for more than 24 inches. Under 24 inches the adjustment does not apply. Grounding conductors never count, and a neutral counts only if it carries unbalanced current, per 310.15(E).

Do ambient correction and bundling adjustment stack?

Yes. When both conditions exist you multiply both factors against the base ampacity. They are not alternatives and you do not use only the worse of the two.

Why is 12 AWG copper limited to a 20 A breaker if the table says 25 or 30?

240.4(D) sets small-conductor overcurrent limits regardless of what the ampacity table allows: 15 A for 14 AWG, 20 A for 12 AWG, 30 A for 10 AWG copper. The higher table values matter for derating headroom, not for the breaker.

Related calculators

Related NEC guides

Start free: 25 questions
No card · 7-day refund
Start →